Instruction Manual
D100345X012
August 2020
1805 Series Relief Valves
!
Failure to follow these instructions or
to properly install and maintain this
equipment could result in an explosion
and/or fire causing property damage and
personal injury or death.
Fisher™ relief valves must be installed,
operated and maintained in accordance
with federal, state and local codes, rules
and regulations, and Emerson Process
Management Regulator Technologies,
Inc. instructions.
If a leak develops or if the outlet
continually vents gas, service to the unit
may be required.
Failure to correct trouble could result in
a hazardous condition. Only a qualified
person must install or service the unit.
Call a gas service person to service the
unit. Only a qualified person must install
or service the 1805 Series Relief Valves.
Introduction
Scope of the Manual
This Instruction Manual provides installation,
adjustment, maintenance and parts ordering
information for 1805 Series relief valves.
WARNING
P1026
Figure 1. 1805 Series Relief Valve
Description
The 1805 Series relief valves are primarily designed
for use in farm tap applications where a safety relief
valve is needed between the first and second stage
regulators. The 1805 Series is suitable for service on
natural gas, air, propane or any operating medium that
is not corrosive to the internal parts. Relief pressure
ranges from 5 to 125 psi / 0.34 to 8.6 bar. Maximum
pressure, including buildup, is 150 psi / 10.3 bar.
1805 Series