Figure 5-10 - Security Screen Login - Enter Passcode
Enter the passcode (the default code is 400 and can be
configured in the E2 under Facility Status Display
General Setup under the Pass Code parameter
(Figure 6-1) and touch Enter to open the first Con-
figuration screen (Figure 5-11).
• Cancel exits the log in screen and returns you
to the Home screen.
• Clear erases the numbers entered in the login
field and allows you to re-enter the passcode.
The FSD Configuration has four configuration tabs
located across the top with three command keys that
appear along the bottom of each configuration screen.
Touch Toggle Keyboard to open an on-screen
"qwerty" style keypad for configuring parameters.
Touch OK to save and exit to the Home screen, Can-
cel to discard changes and exit to the Home screen.

5.4.1. Alarms Tab

Configure alarm information on the Alarms tab with
the following parameters:
• Show RTN Alarms
• Audible Alarm settings
• Show Notices
• Set snooze delay in minutes
• Set minimum alarm priority
FSD Configuration
Figure 5-11 - Alarm Configuration
These alarm parameters can also be set up in the E2
under General setup of the Facility Status Display ap-
plication (Figure 6-1).
Show RTN Alarms
This alarm setting determines visibility of an alarm on
the FSD that has been returned to normal (RTN). For
example, if a case goes into alarm, the FSD will see
the alarm; however, if the alarm returns to normal, the
alarm will not be visible on the FSD, although it is
seen in the individual controller's alarm log as Re-
turn-To-Normal. Enable the checkbox to show re-
turned-to-normal alarms, uncheck to filter out.
Audible Alarm
Audible Alarm will be active any time there is an ac-
tive alarm or a fail advisory displayed. The Audible
Alarm drop-down list allows you to configure the au-
dible alarm buzzer on the FSD with three settings: Ex-
ternal, Internal, and None.
• External is the default. This setting enables the
audible external horn connected to the relay
board as the alarm indicator.
• Internal enables the touch-screen beep as the
alarm indicator.
• None disables all audible alarm indicators.
Show Notices
This notice setting determines whether the FSD will
display notices along with other types of advisories,
or whether these notices will be filtered out of the
FSD. Enable this box to show Notices in the alarm
list, uncheck to filter out.
FSD Screen Navigation • 11