FB3000 RTU HART
®
I/O Module Field Installation Guide
D301918X012
June 2021
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
Notes:
You can/remove replace any I/O module without removing power.
If you replace a 3HRT04 module with another 3HRT04 module, on insertion the new module uses
the configuration of the 3HRT04 module it replaced.
If replacing a module of a different type, for example replacing a 3MIX12 with a 3HRT04, on
insertion you will see a mismatch in FBxConnect. You will need to re-define the module in
FBxConnect as the new module type.
If you have an empty slot that has had no modules defined, on insertion the new module
assumes factory defaults and you must then configure it in FBxConnect.
1.
2.
Removing/Replacing the 3HTSG4 Module
DANGER
Ensure the RTU is in a non-hazardous area. Never open the enclosure in a hazardous area.
DANGER
EXPLOSION HAZARD: Ensure the area in which you perform this operation is non-hazardous.
Performing this operation in a hazardous area could result in an explosion.
2
Depress the orange tabs at the top and bottom of the 3HRT04 module to release the module
and slide it straight out of the slot.
Press the new replacement module into the slot until it is properly seated.