HBUS
Device
Terminate
Cable distance
Cable type
CAT 5e or
better**
BELDEN 9842**
(shielded)
SEC472
SEC4142
* The matching of wire sizes to equivalent wire gauges are only approximate.
** Recommended cable types for optimal HBUS RS485 performance.
Notes:
•
Shielded cable may reduce the obtainable cable length. Shielded cable should be
grounded at the Controller end only.
•
If other cable types are used, operating distances and performance may be reduced
depending on the cable quality.
•
HBUS allows up to 20 readers to be connected to a single cable. Each reader requires at
least 9 Vdc to function correctly. The cable length and the number of readers connected
will have an impact on the voltage at each reader.
3E4288 Gallagher T10 Reader | Edition 1 | August 2016
Copyright © Gallagher Group Limited
"T" or "Star" circuits are
HBUS
not permitted between
Device
HBUS devices
Controller 6000
H1
HBUS
H5
Device
HBUS Module
HBUS
Device
Terminate
Cable format*
HBUS
single reader
connected using
data only in a
single cable
4 twisted pair
500 m (1640 ft)
Each 2 x 0.2 mm
2
(24 AWG)
2 twisted pair
500 m (1640 ft)
Each 2 x 0.2 mm
2
(24 AWG)
4 x 0.2 mm
400 m (1310 ft)
2
Not twisted
pairs (24 AWG)
4 x 0.4 mm
400 m (1310 ft)
2
Not twisted
pairs (21 AWG)
H4
H8
HBUS
Device
HBUS
Device
Terminate
Cardax IV
single reader
connected using
data only in a
single cable
200 m (650 ft)
200 m (650 ft)
200 m (650 ft)
200 m (650 ft)
HBUS
Device
Terminate
HBUS/Cardax IV
single reader
connected using
power and data
in a single cable
100 m (330 ft)
100 m (330 ft)
100 m (330 ft)
150 m (500 ft)
Page 6