Gallagher T15 Mifare Reader Black 사용자 지정 설치 참고 사항 - 페이지 7
{카테고리_이름} Gallagher T15 Mifare Reader Black에 대한 사용자 지정 설치 참고 사항을 온라인으로 검색하거나 PDF를 다운로드하세요. Gallagher T15 Mifare Reader Black 13 페이지.
Gallagher T15 Mifare Reader Black에 대해서도 마찬가지입니다: 설치 참고 사항 (13 페이지)
Cable distance
Cable type
CAT 5e or
better**
BELDEN
9842**
(shielded)
SEC472
SEC4142
C303900/
C303901
Gallagher
HBUS Cable
* The matching of wire sizes to equivalent wire gauges are only approximate.
** Recommended cable types for optimal HBUS RS485 performance.
*** Not applicable for PIV or Bluetooth® enabled reader installations.
**** Tested with 13.6V at start of cable.
Notes:
Shielded cable may reduce the obtainable cable length. Shielded cable should be
•
grounded at the Controller end only.
If other cable types are used, operating distances and performance may be reduced
•
depending on the cable quality.
HBUS allows up to 20 readers to be connected to a single cable. Each reader requires
•
13.6 Vdc to function correctly. The cable length and the number of readers connected will
have an impact on the voltage at each reader.
3
Distance between readers
The distance separating any two proximity readers must not be less than 200 mm (8 in) in all directions.
When mounting a proximity reader on an internal wall, check that any reader fixed to the other side of
the wall is not less than 200 mm (8 inches) away.
200 mm
3E4237 Gallagher T15 Reader | Edition 11 | February 2022
Copyright © Gallagher Group Limited
Cable format*
4 twisted pair each 2 x
0.2 mm
(24 AWG)
2
2 twisted pair each 2 x
0.2 mm
(24 AWG)
2
4 x 0.2 mm
2
Not
twisted pairs (24 AWG)
4 x 0.4 mm
2
Not
twisted pairs (21 AWG)
2 Twisted pair each 2
x 0.4 mm
(21 AWG,
2
Data) and 2 x 0.75
Not Twisted Pair
2
mm
(~18 AWG, Power)
HBUS
Cardax IV
single reader
single reader
connected
connected
using data
using data
only in a single
only in a single
cable
cable***
500 m (1640 ft)
200 m (650 ft)
500 m (1640 ft)
200 m (650 ft)
400 m (1310 ft)
200 m (650 ft)
400 m (1310 ft)
200 m (650 ft)
500 m (1640 ft)
200 m (650 ft)
HBUS/Cardax IV
single reader
connected using
power and
data in a single
cable****
100 m (330 ft)
100 m (330 ft)
100 m (330 ft)
150 m (500 ft)
450 m (1490 ft)
Page 7