Galletti CSW 246 DF 기술 매뉴얼 - 페이지 8

{카테고리_이름} Galletti CSW 246 DF에 대한 기술 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Galletti CSW 246 DF 20 페이지. Csw water cassette
Galletti CSW 246 DF에 대해서도 마찬가지입니다: 설치 및 유지 관리 매뉴얼 (20 페이지)

Galletti CSW 246 DF 기술 매뉴얼
CSW
7

SOUND LEVELS

Vr
Fan speed:
3=maximum
2=medium
1=minimum
Lw
Octave band sound power level
Lw
A - weighted sound power level
A
Lp
A - weighted sound pressure level (1m distance, 4 directional factor)
A
CSW - CSW DF
CSW 136 - CSW 136DF
CSW 186
CSW 246 - CSW 246DF
CSW 249 - CSW 249DF
CSW 369
CSW 489 - CSW 489DF
8

HYDRAULIC CONNECTIONS

Position and diameter are reported as shown in the picture below.
When a piping is connected to the unit main body or removed from it, be sure to use two wrenches to fasten it.
Carefully insulate pipes, valve assemblies and coil connections to avoid condensation forming on the pipes and dripping on the false ceiling.
CSW 136-186-246
drain outlet pipe
CSW 249-369-489
drain outlet pipe
MODELS
water inlet
CSW 136
CSW 186
CSW 246
CSW 249
CSW 369
CSW 489
WC66000067-REV.00
125 Hz
250 Hz
Vr
dB
dB
50,3
50,1
max
40,2
42,1
med
32,6
34,0
min
54,7
53,5
max
44,8
44,3
med
36,8
36,2
min
57,5
60,3
max
53,9
51,2
med
42,0
43,9
min
58,8
54,8
max
53,1
49,3
med
49,8
46,7
min
57,5
57,9
max
54,0
53,4
med
54,0
50,3
min
63,4
66,0
max
59,6
62,6
med
56,9
61,0
min
air purge
water outlet
water inlet
drain valve
air purge
water outlet
water inlet
drain valve
water outlet
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
1"
1"
1"
1"
All copying, even partial, of this manual is strictly forbidden
Lw
500 Hz
1000 Hz
2000 Hz
4000 Hz
dB
dB
dB
47,7
43,3
38,4
38,8
32,9
29,7
30,9
22,7
26,8
52,3
47,7
41,9
41,9
36,1
31,5
31,8
23,2
25,8
59,5
55,7
50,3
50,4
45,8
38,9
42,0
36,1
29,8
50,2
46,7
50,0
45,9
44,5
45,6
42,6
43,2
40,0
52,7
49,3
54,4
49,7
46,3
52,1
46,6
44,2
49,7
53,8
50,7
52,3
51,3
47,7
50,5
48,8
45,4
48,6
drain outlet pipe
drain outlet pipe
MODELS
chilled water
inlet
CSW 136 DF
3/4"
CSW 246 DF
3/4"
CSW 249 DF
3/4"
CSW 489 DF
8
8000 Hz
LwA
LpA
dB
dB
dB/A
dB/A
28,4
18,8
49,0
44
17,5
17,7
40,0
35
15,8
16,9
33,0
28
32,1
22,8
53,0
48
18,6
17,8
42,0
37
15,4
16,7
33,0
28
43,7
34,0
61,0
56
29,0
20,8
51,0
46
17,5
18,0
42,0
37
31,9
19,7
55,0
50
26,8
18,0
51,0
46
21,4
17,7
47,0
42
42,7
30,0
58,0
53
36,5
23,6
55,0
50
32,1
20,3
53,0
48
42,9
32,5
60,0
55
37,5
26,3
57,0
52
33,5
22,8
55,0
50
CSWDF 136-246
air purge
water outlet
water inlet
drain valve
CSWDF 249-489
air purge
water outlet
water inlet
drain valve
chilled water
hot water
outlet
inlet
3/4"
1/2"
3/4"
1/2"
1/4"
1/2"
1"
1"
3/4"
hot water
outlet
1/2"
1/2"
1/2"
3/4"