Wall-Mounted Dewpoint Sensor
2. Highlight the input-point the sensor is
attached to and press
up the input, or press
Actions Menu and select 5 (Setup). (If using
an Einstein, select an input point and press F7
(SETUP IN) to open the Analog Input screen.)
E2 Actions Menu for Selected Input
3. Select Analog to set up the input as analog.
The Analog Input screen will display:
Set Sensor Type to Linear
4. Once on the Analog Input screen, move the
cursor to the Sensor Type field, press
(LOOK UP), and set to Linear. (If using
Product Information Sheet
(SETUP) to set
to open the
48
an Einstein, press F7 (LOOK UP) and set to
Linear.)
Option List Selection Menu For Sensor Type
5. Move cursor to Select Eng. Units and press
(LOOK UP). Set this field to DF (for
Degrees Fahrenheit). (If using an Einstein,
press F7 (LOOK UP) and set to DF.)
Set Sensor Type to Linear
6. Then set the following sensor properties:
Set the Modify field to: EndPoint. (If
using an Einstein, press F7 (LOOK UP)
and set to EndPoint.)
210-2002