EM REMOTE / FIRE PANEL
Connections for remote emergency shut-off buttons or integrated with a fire alarm to close the gas
supply automatically in the event of a fire. This is linked out as a factory setting.
Remote emergency shut-off buttons should be dry contact and wired to the using a plenum security
cable, white, 18/2 (18AWG 2 conductor), stranded, CMP or similar.
WIRING GAS DETECTORS
Refer to your gas detector manual for further information!
If no detector is being used leave the factory fitted link in!
Connecting a Gas Detector i / i-S
Connecting a Gas Detector