Merlin 1000Si
2

Circuit Board Terminals

2.1

LINE VOLTAGE

A 110-120VAC electrical supply should be externally fused at 3A
and connected to the terminals marked [LINE VOLTAGE LNE].
2.2

VALVE OUT

The 110-120VAC gas solenoid valve should be powered using
the terminals on the Merlin 1000Si detailed [VALVE OUT LNE].
This is a relay that changes state in alarm or when the gas is on/off and can
be used in conjunction with the 12vDC output and other external relays that
affect other devices and controls such as purge fans and audible alarms etc.
2.4
This terminal is for remote emergency shut-off buttons and detailed on the
circuit board as [EM REMOTE].
This is linked out as a factory setting.
Remote emergency shut-off buttons should be volt free and wired to the
Merlin 1000Si using a plenum security cable, white, 18/2 (18AWG 2
conductor), stranded, CMP or similar.
2.5

GAS DETECTOR

These connections can be wired to a Merlin gas detector (LPG,
natural gas or carbon monoxide) as shown.
If no detector is being used leave the link in between the "
Refer to your detector guide for more information.
Rev: 05
05-19
2.3

BMS OUT

Terminal connections are available on the circuit board for Building
Management systems etc.
Detailed on the circuit board as [BMS OUT - N/C, COM and N/O]
(Normally Closed / Common / Normally Open).
These are volt free connections.

EM REMOTE

".
User Guide
4