Gas Fill Time and Prove Time
FILL TIME: Amount of time the gas valve opens to fill the gas line on power up or reset.
PROVE TIME: Amount of time the system tests the gas line for leaks on power up or reset.
There are two switches located on the circuit board labelled [FILL TIME] and [PROVE TIME].
FILL TIME
OFF
5 Seconds (Default)
ON
10 Seconds
Once the settings have been changed - remove power for 10 seconds.
Fire Panel Integration
The Merlin 1000SW+ can be integrated with a fire alarm to close the gas supply automatically in
the event of a fire. The volt free fire alarm signal can be wired in series with any remote
emergency shut off buttons.
If there are no remote emergency shut off buttons being installed, wire this directly to the
terminal marked [EM REMOTE].
Auto Shut-Down - Timeout Period
The system has an auto-shut down feature after a selected time.
There are two switches located on the circuit board labelled [TIME1] & [TIME2].
These can be configured to select the required timeout/ shut-down period.
TIME 1
TIME 2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Note:
Upon timeout the gas supply will be turned off unless other utilities are
1000SW+ IOM Rev: 09
OFF
ON
Timeout Period
2 Hours (Default)
4 Hours
8 Hours
Disabled
01-20
PROVE TIME
30 Seconds (Default)
50 Seconds
Merlin 1000SW+
configured.