Galvin Engineering Haws GalvinSafe Axion 8100-A 제품 설치 매뉴얼 - 페이지 5

{카테고리_이름} Galvin Engineering Haws GalvinSafe Axion 8100-A에 대한 제품 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Galvin Engineering Haws GalvinSafe Axion 8100-A 6 페이지. Free standing drench shower, pull rod, msr abs shower

TROUBLESHOOTING

PROBLEM
1. No Flow.
2. Insufficient water flow at shower
3. Water does not drain properly.
4. Water leak between joints or fittings.
For more information about GalvinSafe
1.
Check the main shut-off valve.
2. a. Verify minimum 210 kPa flowing supply
line pressure.
b. Probable clogging of flow control
inside shower head. Unscrew shower head
off elbow and clean rubber flow control.
3.
Check your drain system for debris. Check
the main waste line of your building to see
if it does handle the capacity required for
the entire drainage system
4.
Tighten loose connections. If leak persists,
the application of hot water will sometimes
reseat improperly applied joint compound.
After 30 minutes wait and retest. A
persistent leak will necessitate reassembly
and additional sealant.
®
(Haws) products, see our website.
th
Version 3.2, 21
Sept. 2021, Page 5 of 6
REPAIR CHECKLIST