AGS Parksafe Control Panel 설치 운영 및 유지보수 - 페이지 7

{카테고리_이름} AGS Parksafe Control Panel에 대한 설치 운영 및 유지보수을 온라인으로 검색하거나 PDF를 다운로드하세요. AGS Parksafe Control Panel 16 페이지. Ventilation control panel
AGS Parksafe Control Panel에 대해서도 마찬가지입니다: 설치 및 운영 매뉴얼 (16 페이지), 설치 및 운영 매뉴얼 (16 페이지), 설치, 운영 및 유지보수 매뉴얼 (20 페이지)

AGS Parksafe Control Panel 설치 운영 및 유지보수
Installation, Operation & Maintenance

Wiring a Detector

Power and Modbus data are wired between detectors with the first connected
to a control panel DETECTOR CHAIN terminal. If using a shielded wire
(recommended) then connect the shield to [-] power terminals.
problem is likely related to grounding, incorrect shielding or wiring mains power next to Modbus wiring.
To ground the data cable, the shield should be connected to [-] of the chain terminals.
Reversing the [D+] and [D-] connections of any device can lead to the whole system to stop working owing to reverse
polarity found on the terminals.
The detector must be earthed/grounded for electrical safety and limit the effects of R/F & EMC interference!
Ensure the 120-ohm termination resistance switch is on at each end of a cable run!

Wiring a Detector Chain

Up to 16 Parksafe detectors can be connected, chained in a parallel 'daisy chain' method up to approx. 500 yards from
the panel depending on chain configuration, wire type for power and condition. Any other way may cause issues or
damage to the overall system. It is recommended that the cable of same color should be used to connect all [D+]
terminals together and similarly cable of same color to be used to connect all [D-] terminals together.
Split chain example from a Parksafe Control panel.
Rev: 13
0721
For MODBUS communications, a shielded cable is used.
The shielding can be of 2 types: braided [mesh of thin conducting wires] or
foil (consisting of a thin sheet of metal covering the twisted wires).
One example of such cable is BELDEN 3082A.
If you are encountering noise or irregular problems with a Modbus link, the
Single chain example from the Parksafe Control Panel.
Parksafe Control Panel
7