AGS Merlin 1000S+ 사용자 설명서 - 페이지 10

{카테고리_이름} AGS Merlin 1000S+에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. AGS Merlin 1000S+ 12 페이지. Gas and electric isolation controller
AGS Merlin 1000S+에 대해서도 마찬가지입니다: 설치 운영 및 유지보수 (12 페이지)

Merlin 1000S+
6

1000S+ Wiring Spec

1
2
L
N
E
Gas Valve
1. LINE VOLTAGE: Mains Input 110-120VAC Single Phase.
2. VALVE OUT: Gas Solenoid Valve Power Output, 110-120VAC, Max 3A.
3. ELECTRIC CONTACTOR: Power Output, 110-120VAC, Max 3A.
4. WATER VALVE: Disabled on this system.
5. SUPPLY FAN PD SWITCHES: Disabled on this system.
6. EXTRACT FAN PD SWITCHES: Disabled on this system.
7. BMS OUT: Normally Closed, Common and Normally Open.
8. PRESSURE SENSOR: Gas pressure transducer, power supply and returned signal (supplied).
9. EM REMOTE: Remote emergency stop buttons and Fire Alarm input wired in series
(purchased separately). VOLT FREE INPUT
10. GAS DETECTOR: Power supply and VOLT FREE INPUT (detectors purchased separately).
11. FS 1/ 2/ 3: Fan Switch output (purchased separately).
12. CO2 MONITOR: (purchased separately). VOLT FREE INPUT
13. 12VDC: Permanent output when there is power at the panel. 50mA max
Rev: 06
05-19
3
4
L N E
5
6
7
Pressure
Transducer
EM
Stop
User Guide
8
9
10
11
Gas
Detector
Monitor
12 13
CO2
10