Galvin Specialised CliniLever TCWMC80PC 매뉴얼 - 페이지 3
{카테고리_이름} Galvin Specialised CliniLever TCWMC80PC에 대한 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Galvin Specialised CliniLever TCWMC80PC 4 페이지. Healthcare tapware
3. Fit water temperature indicator
−
®
Once CliniLever
lever handle is secure, fit
the water temperature indicator.
−
Ensure the set is installed with hot and cold
in the correct location.
TROUBLESHOOTING
PROBLEM
Taps are dripping water
Water is leaking from spindle
Water is not flowing from tap
Spindle is difficult to turn
(jumper valve)
Handle is loose
Flange does not screw down
onto basin/sink surface
4. Testing
−
CAUSE
Jumper valves are worn or damaged
Ceramic discs are worn or damaged
Tap seat is damaged
O-ring on jumper valve spindle is
damaged or worn
Water is turned off
Aerator or flow regulator is blocked by
debris
Build up of scale on spindle, spindle
worn or o-ring has been damaged
Screw has come loose
Tap bodies are set too far out
Version 2, 18 July 2017, Page 3 of 4
Once temperature indicator is fitted, check the
operation of the unit and inspect for any leaks.
RECTIFICATION
Replace jumper valve
Remove and inspect SBA.
Remove debris and/or replace
SBA if damaged.
Refurbish tap seat using a
reseating tool.
Replace o-ring
Turn water on
Remove aerator and/or flow
regulator from tap and remove
debris. Install an inline strainer.
Remove jumper valve, clean and
regrease. Replace o-ring.
Complete SBA may need to be
replaced.
Tighten handle screw
Re-position tap bodies and breach
piece