AGS Merlin 1500S 사용자 설명서 - 페이지 8

{카테고리_이름} AGS Merlin 1500S에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. AGS Merlin 1500S 12 페이지. Gas & ventilation interlock system
AGS Merlin 1500S에 대해서도 마찬가지입니다: 사용자 및 설치 매뉴얼 (8 페이지), 설치 및 운영 매뉴얼 (12 페이지)

AGS Merlin 1500S 사용자 설명서
Merlin 1500S
4

Panel LED status

When the system is connected to the mains supply, the Red LED of the AGS Logo located in the
bottom right corner of the panel will illuminate.
When no power is present, this LED will not light up.
Gas On
When the fans are running at the correct speed and the key switch is turned on, the Merlin 1500S
will open the gas valve and the green 'Gas On' LED will illuminate.
ON = Gas On
OFF = Gas Off
Supply Fans
Under normal working the LED will illuminate GREEN. If a supply fan fault is detected, the LED will
be flashing.
ON = OK
FLASHING = One of the supply fans is not running.
Extract Fans
Under normal working the LED will illuminate GREEN. If an extract fan fault is detected, the LED
will be flashing.
ON = OK
FLASHING = One of the extract fans is not running
IF SUPPLY AND/OR EXTRACT FANS LED FLASHES FOR MORE THAN 20 SECONDS, THE GAS WILL SHUT OFF.
Rev: 07
05-19
User Guide
8