Installation, Operation & Maintenance

Mounting

Unpack all the parts!
This device is designed for either surface mounting, or mounted on a one or two gang electrical box and
must be installed by a licensed, insured contractor.
This device comes with a deep base back cover and barrier slip to maintain segregation between high
and low volt connections.
A flush mount base is available – Contact your supplier for more information.
1. Carefully remove the rear cover from the unit by releasing the two latching clips with a small flathead
screwdriver.
2. Using the rear cover - mark the screw holes to the wall or align with the electrical box. If mounting
direct to wall - ensure the wall surface is flat to prevent base distortion.
3. There are pre-fractured areas for cable entry and barrier to separate low and high volt connections.
4. Mount at 5 feet from ground level and in accordance with any applicable regulations.
5. After executing the mounting and connections – secure the rear cover.
Take care when making connections to high voltage connectors!
Any damage attempting to remove the circuit board may void any warranty!
All Class 2 wiring is to be installed within flexible tubing to maintain segregation between circuits!
Wiring of different circuits shall be separated by means of routing, clamping or barrier!
All wiring shall be made of copper!