Mini Merlin Installation, Operation & Maintenance

Bump Test Procedure

To increase reaction time, cover the escape vents at the sides of the device.
Always remove the regulator/valve if using a cylinder after use!
Always give at least five (5) minutes between testing the same unit or until gas has fully dispersed!
Always consider safety and use equipment in accordance with Safety Data Sheets!
Reference should always be given to any applicable national & local law and industry codes.
Generally, the gas concentration should be greater than the alarm threshold of the device.
Always remove the regulator/valve after use if using a cylinder!
All cylinders will re-seal upon removal of the regulator/valve!
Deviating from this test process is deemed improper and may affect the functional safety of your device!
Exposure to chemicals, smoke, or any other materials other than the gases intended to be monitored can seriously damage
the gas sensing elements!
Always allow a minimum of 5 minutes before testing the same unit!
Ensure you have the correct gas for the device type prior to application.
1.
Offer up the applicator hose/cone or spray and apply to the small vents of the device located underneath.
2.
Apply gas.
3.
The device will enter alarm status after reaching alarm set point.
4.
The device will activate all configured outputs/relays.
5.
At this point...
Remove applicator hose/ cone or spray.
6.
Reset by pressing the touch sensor.
7.
Test complete.
8.
Record your test details.
9.
Rev: 03 05-22
13