AGS Merlin GDP2 사용자 설명서 - 페이지 5

{카테고리_이름} AGS Merlin GDP2에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. AGS Merlin GDP2 12 페이지. Safe area gas detector controller
AGS Merlin GDP2에 대해서도 마찬가지입니다: 사용자 및 설치 매뉴얼 (7 페이지), 설치 운영 및 유지보수 (12 페이지)

AGS Merlin GDP2 사용자 설명서
Merlin GDP2
2.4

EM REMOTE (Remote emergency shut off buttons)

The terminal for remote emergency shut-off buttons is detailed on the
circuit board as [EM REMOTE].
These connections are linked out as a factory setting. Remote
emergency shut-off buttons should be volt free and wired to the Merlin
GDP2 using two-core cable.

2.5 HEAT SENSOR

The terminal for heat detectors is detailed as [HEAT SENSOR].
These connections are linked out as a factory setting.
Heat detectors should be volt free and wired to the Merlin GDP2 using two-
core cable.
2.6

FIRE PANEL

The terminal for fire alarms is detailed as [FIRE PANEL].
These connections are linked out as a factory setting.
Fire alarms should be volt free and wired to the Merlin GDP2 using two-
core cable.
2.8

SOUNDER/STROBE

The terminal for audible/visual alarms is detailed on the circuit board as
[SOUNDER/STROBE].
Sounder alarms should be wired using low voltage cable and wired to the
Merlin GDP2 using two-core cable.
This terminal has a 24VDC output.
Rev: 05 05-19
2.7

BMS OUT

Terminal connections are available on the circuit board for connections
to Building Management Systems etc.
Marked on the circuit board as [BMS OUT - N/O - COM - N/C] these are
volt free connections.
User Guide
5