10. OPERATING LIMITS
If the appliance is supplied with chilled water, the condensation forming on the heat exchanger will
be drained via the condensation drain connection.
At very low chilled water temperature and very high humidity, condensation may form on compo-
nents other than the heat exchanger. This is not collected in the condensation drain, but might drip
from under the appliance.
To avoid this, a minimum permitted water temperature must be taken into account in function of the
relative humidity and temperature of the ambient air.
10.1. PERMITTED MINIMUM WATER TEMPERATURE (°C)
40 %
50 %
60 %
70 %
RH (%)
80 %
90 %
100 %
9. INSTALLATION
For general safety information see: warnings and safety - page 61
Always use the main switch to de-energize the power supply !
ATTENTION! The device must remain accessible at all times for maintenance. in the case of
Bottom or ceiling installation, the enclosure must always be disassembled for service purposes.
The unit has sharp edges; always wear gloves.
01
Mark the fastening points, using those on the unit or according to the dimensions specified on page 8 and 10 in this manual. Slightly
tilt towards the condensate drain to help the water drain. Respect the free space around the unit as shown on page 7-11. The type of
wall/ceiling determines what type of screw or plug should be used. For installation on drybottom: make sure that the holes line up with
supporting studs.
12
AMBIENT TEMPERATURE / DRY BULB TEMPERATURE (°F)
69.8 °F
73.4 °F
°F
°F
37.4
37.4
°F
°F
37.4
37.4
°F
°F
37.4
37.4
°F
°F
37.4
39.2
°F
°F
39.2
41
°F
°F
41
42.8
°F
°F
42.8
46.4
Wall
77 °F
80.6 °F
°F
°F
37.4
37.4
°F
°F
37.4
37.4
°F
°F
39.2
39.2
°F
°F
41
42.8
°F
°F
42.8
46.4
°F
°F
46.4
50
°F
/
50
Permitted minimum water temperature
84.2 °F
87.8 °C
°F
°F
37.4
39.2
°F
°F
39.2
42.8
°F
°F
42.8
46.4
°F
°F
46.4
50
°F
/
50
/
/
/
/
Ceiling