Calibration
Due to variations in supply parameters from those used to set and test the
products in our factory the outlet temperature will require resetting on site. The
temperature will need to be set between 39ºC and 41ºC in order to comply with
TMV3 approval this is done by fully opening the valve, using a thin blade
remove the indice holder (45) with indice (46) still attached. Then inserting a
2.5mm hexagon wrench into the adjusting screw (32) and turning the screw
clockwise for a cooler temperature and anti clockwise for a warmer temperature
see Fig 1
Fig 1
Operation
The unit has a single control lever that turns the unit on and off and adjusts the
temperature. Turning the handle anti clockwise from the off position firstly gives
cold water flow then increases the temperature to the maximum set value.
Maintenance
This product is designed to be easily serviced, it has integral isolation, integral
hot water flushing to pasteurise the mixed water chambers reducing the
incidence bio film growth and unions that allow the complete body to be
removed for servicing in the workshop.
Isolating and removal of the valve
The valve has integral isolation this is accessed by unscrewing the shroud (13)
and pulling it back along the elbow taking care not to scratch the chrome, the
2.5mm hexagon wrench is inserted in the isolating plug (6) and rotating it
clockwise until it locks. The securing nut (14) is then removed whilst supporting
the valve to stop it falling and damaging the surface below it. The valve can then
be replaced or serviced as is most convenient. The valve is replaced by reversing
the above procedure ensuring the O-ring is undamaged and in place.
Insert isolator
and turn
Fig 2
The purpose of this section is to ensure the valve is adjusted correctly for the
system in use.
The supply pressures and temperatures should be checked to ensure they are
within the requirements of DO8 and the flow limiters set as per the above table
The fitting should be run for several minutes until the mixed water and incoming
water temperatures have stabilised, the mixed water temperature should be
adjusted as per the calibration section above,
The cold water to the fitting should be isolated the mixed water flow should
reduce to a drip or small run, the cold water reinstated and the temperature
should recover close to the original temperature.
The following information should be recorded
a) The temperature of incoming supplies.
b) The temperature of mixed water outlet under normal running.
c) The temperature of any residual flow after cold isolation.
d) The temperature of mixed water outlet under normal running after
isolation.
e) Record the identity of all instruments used.
The thermostatic mixing valve (TMV) will be installed in such a position that
maintenance of the TMV and its valves, and the commissioning and testing of
the TMV can be undertaken
The fitting of isolation valves is required as close as is practical to the water
supply inlets of the thermostatic mixing valve.