4. Safety components
The burner is equipped with several safety mechanisms:
-
Backfilling sensor / temperature gauge on inlet tube that is installed tube for connecting of
pellet feeding flexible tube. At excessive temperature on feeding tube error E3 is displayed at
control unit (LED diode
control unit (LED diode
Backfilling sensor in normal mode (green LED flashing while the other depending on the amount of
Backfilling sensor in a mode where the registered supply pipe backfilled with pellets
(all LEDs light for 10 seconds without blinking, the regulation is displayed error E9)
-
Safety pressure switch built in the burner controls overpressure in the boiler combustion
chamber. If the set overpressure in the boiler combustion chamber is exceeded, pressure
switch stops feeding of pellets, the burner shut down and the error E1 is displayed at control
unit (LED diode
-
If lower boiler door are opened while the burner is working, micro switch on lower boiler door
cuts the el. power to the control unit and burner. After closing the lower boiler door control unit
continues to work according power supply interruption regime.
-
If there is no flame (the built in photo-cell does not detect the flame within set time), control
stops the burner operation and error E2 is displayed or it goes to blowing off and error E6 is
displayed (LED diode
-
Control unit has a built in protective function which protects the boiler against overheating. If
temperature in the boiler exceeds 93
boiler pump and/or the sanitary water turns on and works until temperature in the boiler falls
0
below 93
C.
When temperature in the boiler exceeds 110
thermostat (via control unit).
Thermal protection built in coils of the fan electric motor at the burner and the screw feeder motor,
protects them against overheating caused by failure or locking.
switched on). At backfilling supply tube error E9 is displayed at
switched on).
pellets that fall through the supply tube)
switched on).
switched on).
0
C, regardless heating or sanitary water is needed the
°
C (+0°C / - 9°C), power supply is turned off by the safety
Technical instructions Cm Pelet-set
5