Major tech MT745 사용 설명서 - 페이지 7

{카테고리_이름} Major tech MT745에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Major tech MT745 8 페이지. Flexible ac current trms clamp meter

Major tech MT745 사용 설명서
INRUSH Button
INRUSH current measurement function, is in the manual measurement mode. The
need for the operator to predict the value of the inrush current and then select
the appropriate measuring range, to ensure the accuracy of the measurement.
Ÿ Press the "INRUSH" key to enter "INRUSH" measurement mode, LCD screen
displays "----", at this time the instrument is preset in the 3000A range.
Ÿ After entering the INRUSH measurement mode, hold down the "INRUSH"
key, it will then convert to a 30A measurement range; hold down again, it will
then convert to a 300A measurement range; hold down again, it will then
convert to 3000A measurement range.
Ÿ The preset range, starting with electrical equipment, inrush current value will
remain on the LCD screen. If you want to measure again, you need to re-enter
the measurement model.
Ÿ Enter the "INRUSH" mode, and then press the "INRUSH" key, you can exit
the measurement model.
LOG Button
Press the LOG key, the meter will display
changes in the known period of time data, and store it on the meter for the
Mobile APP to read and analyze. Hold down the
the meter will display , the data will be sent to the Mobile APP in immediately.
With Bluetooth active, hold down the LOG key, the meter will display "SEND",
you can send the data stored in the data to the Mobile APP, select send the
complete automatic return to the measurement mode.
Note: Bluetooth Connect:
1. Turn on the Bluetooth function on the instrument using Menu Button
2. Turn on the Bluetooth of the Smartphone, press the Meterbox Pro icon and
enter into the home interface. Then press Connect Device icon on the home
interface, Bluetooth device name will appear.
3. Touch the device name listed in Bluetooth devices list to connect the meter.
Meterbox Pro for Android & iOS: Please search in the app stores with
keyword Meterbox Pro, download and run.

Maintenance

Cleaning and Storage
Wipe the case with a damp cloth and mild detergent; do not use abrasives or
solvents. If the meter is not going to be used for more than 60 days, remove
the battery.
Battery Replacement
Remove the Phillips head screw that secures the rear battery door.
Ÿ
Open the battery compartment and replace the two 1.5V AAA batteries.
Ÿ
Secure the battery compartment.
Ÿ
and will begin to record the current