TROUBLESHOOTING
SYMPTOM
1
Outdoor air coming to
the dwelling is cold.
2
Supply air fan keeps
stopping.
Supply air fan stops and
3
starts too frequently.
The maintenance reminder
4
symbol ( ) is displayed and
the unit operates otherwise
normally.
"Exh air sensor faulty"
5
message is displayed and
the unit is stopped.
"Inp. air sensor faulty"
6
message is displayed and the
unit is stopped.
"In air sensor faulty" message
7
is displayed and the unit is
stopped.
"Out air sensor faulty"
8
message is displayed and the
unit is stopped.
DV 90 SE
REASON
• Air cools down in the attic ducts.
• The heat recovery cell is frozen, which is
why extract air cannot heat outdoor air.
• The post-heating radiator does not work.
• The extract air filter or cell is clogged.
• The initial adjustment of ventilation has not
been done.
• The stopping of the supply air filter is acti-
ve.
NOTE!
If you decrease the setpoint too much, the cell
may freeze. Compare with list item 1.
• The difference between the stopping and
starting temperatures is too small.
• The maintenance reminder lights up the
service reminder symbol in the main
display of the control panel at an interval
of approximately 4 months (factory set-
ting).
• You may change the interval (see the
instructions for using the control panel, sec-
tion 3.3.18).
• There is a fault in the freezing protection
sensor.
• There is a fault in the supply air sensor.
• There is a fault in the extract air sensor.
• There is a fault in the outdoor air sensor.
DO THIS
• Check the insulation of the attic ducts.
• If the heat recovery cell is frozen, check the setpoint for
freeze protection. The setpoint for freeze protection can be
raised by 1 or 2˚C, or the sensor can be bent closer to the
cell, in which case the supply air fan stops earlier (see the
instructions for using the control panel, section 3.3.20).
Thaw the cell before closing the door.
• Check that the filters and the heat recovery cell are clean.
• The fan stops more rarely and the efficiency of the heat
recovery cell gets better when the setpoint is decreased by
1 or 2˚C. (See the instructions for using the control panel,
section 3.3.20.)
• Raise the difference between the stopping and starting tem-
peratures by 1 or 2˚C. It extends the period between stop-
ping and starting. (See the instructions for using the control
panel, section 3.3.19.)
• Check the cleanliness of the filters and the unit. If needed,
clean or replace the filters. Also check the external grille.
• Acknowledge the maintenance reminder symbol to make it
disappear. (See the instructions for using the control panel,
section 3.3.7.)
• Contact a maintenance company. The sensor installation
must be checked and if necessary the sensor replaced.
• Contact a maintenance company. The sensor installation
must be checked and if necessary the sensor replaced.
• Contact a maintenance company. The sensor installation
must be checked and if necessary the sensor replaced.
• Contact a maintenance company. The sensor installation
must be checked and if necessary the sensor replaced.
14