Major tech MT330 사용 설명서 - 페이지 7

{카테고리_이름} Major tech MT330에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Major tech MT330 12 페이지. Digital earth resistance tester

Major tech MT330 사용 설명서

7. BUTTON FUNCTION OPERATION

7.1. HOLD FUNCTION

The hold function freezes the reading in the display. Press the HOLD
key momentarily to activate or to exit the hold function

7.2. BACKLIGHT

Press the
backlight will automatically turn off after 15 seconds.
8. MEASUREMENT OF EFFECTIVE RESISTANCE OF EARTH
ELECTRODES
BEFORE PROCEEDING MEASUREMENT, READ SAFETY NOTES ON
PAGE 4.
1. In proceeding with measurement, if symbol appears on the display,
replace with new batteries.
2. Short the tips of the leads and press the "TEST" button. Adjust the 0Ω
"ADJ" turn cap control to set the reading of zero.
3. Rotary to function switch to "EARTH VOLTAGE" position and press to
test. Earth voltage will displayed on the LCD. When earth voltage is
more than 10V, it may result in errors in earth resistance measurement.
Accurate earth resistance measurement may not be made.
4. Precision earth resistance measurement method :
(1) Connect green, yellow and red test leads to instrument terminals E, P
and C with auxiliary earth spikes P1, C1 stuck into earth "IN A
STRAIGHT LINE ".(Fig.1)
(2) Rotary the function switch to suitable range then press the push
button to test and take the reading.
key for to turn on the display backlight function. The
7