Gammon GTP-9330-101 설치 및 운영 - 페이지 2

{카테고리_이름} Gammon GTP-9330-101에 대한 설치 및 운영을 온라인으로 검색하거나 PDF를 다운로드하세요. Gammon GTP-9330-101 4 페이지. One-cc water probe

Gammon GTP-9330-101 설치 및 운영
GAMMON TECHNICAL PRODUCTS, INC.
INSTRUCTIONS: INSTALLATION AND OPERATION
ONE-CC WATER PROBE
GTP-9330
2. Make an electrical connection to the
L-type conduit body mounted on the
side
of
the
assembly.
3. Connect the black wire from the
GTP-9330 probe to a ground wire
using a wire nut. The yellow wire
connects to the intrinsically safe
power
Note: The IS relay may be wired by the
installer to the deadman system to stop
fuel flow, provide an audible warning,
and/or provide a visual signal such as a
red light labeled "water in sump."
OPERATION
The GTP-9330 will constantly monitor for presence of water. Function of the probe can be tested
using the following procedure while the fuel system is in operation.
1. Remove
the
aluminum cap from the probe
housing. This causes the internal
mechanism to shift into the test
position.
2. The test water injection pump has
two sections; a cylinder and piston.
Rotate both sections together ¼ turn
counterclockwise and then pull to
remove the entire pump assembly.
GTP-9330
probe
wire.
large
gold-colored
INSTRUCTION 6414
REVISED 6/20/18
Page 2 of 4