The pump must be earthed. It is suitable
for connection to a 230v 50hz AC
power supply using the Supply Cable
provided. Connection to the electrical
supply must be via a double pole isolation
switch having a separation of at least
3mm in each pole (Brown
Blue = Neutral, Green/Yellow = Earth).
The two black wires are for connection of the
internal hi-Level safety switch. The switch
has a maximum rating of 3 amps and can
be used to stop the air conditioning
system in the unlikely event of pump
failure and should always be utilised.
This pump must be installed and
commissioned by a competent person in
accordance with these instructions.
Following installation and commissioning,
the operation of this pump should be
explained to the user and these instructions
left with them for future reference.