These installation and operation instructions
apply to the following temporary power
branch distribution system components. Do
not discard these instructions, save for future
Reference.
P OR T AB LE P OWE R
DIS T R IB UT ION UNIT S
These units are rated either 20 or 30 amps,
125/250 VAC, Single Phase. The max. ampacity
for the 20 amp unit is 40A @ 120V, and the 30
amp unit is 40A @ 120V. The 20 amp, 120 volt
outlets are individually protected by circuit
breakers and GFCI circuit modules.
Model
Number(s)
6502GU,6503GU
99577,99577C
6502GTL, 6503GTL
INT R ODUC T ION
CEP temporary power distribution units equipped
with GFCI modules that will protect you from
electrocution hazards resulting from ground
faults. Ground faults are current leaks and can
result in electric shock. Currents of o
of an ampere can be fatal. The GFCI protection
provided by CEP temporary power distribution
temporary power distribution units,
Ph: 800-474-7570, 602-272-8128 Fax: 602-272-8014
www.BestMaterials.com Email: [email protected]
Distributed by Best Materials® LLC
99577, 99577C
T emporary branch power dis tribution unit
with G round F ault P rotection for pers onnel
Installation and Operating Ins tructions
20 Amp
Receptacle
U-Ground
Twist Lock
nly 60/1000
which are UL listed as Class A, Group I
interrupters, respond to fault currents as low as
3-6 mill amperes , and will shut of the current
within 1/40
of a second. The temporary power
th
distribution unit is designed to provide protection
against electrical shock hazards due to line
ground faults. Although the GFCI module does
not eliminate the hazard of a shock, it does limit
the duration of t he shock to a period considered
safe for normally healthy persons.
GFCI modules will provide protection against
ground faults only. They will not protect against
overloads or short circuits. There is no known
device that will guard against the electrical s
hazard resulting from contact with both the "hot"
and neutral wires of the electrical circuit.
E LE C T R IC IT Y IS DANG E R OUS .
E V E N WHE N S AF E T Y DE V IC E S AR E
P R E S E NT , HANDLE WIT H C AR E AND US E
R E AS ONAB LE C AUT ION.
LE T C AUT ION P R E V AIL
The CEP temporary power
designed to be used on a grounded electrical
supply system. It will not operate when supplied
from a power source which is not grounded.
Over -current protection of the proper rating,
according to the National Electric Code, Article
240, must be used on the supply circuit feeding
the temporary power distribution units.
.