E-T-A ESX10-TA-DC 24 V 사용 설명서 - 페이지 3

{카테고리_이름} E-T-A ESX10-TA-DC 24 V에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. E-T-A ESX10-TA-DC 24 V 8 페이지. Electronic circuit protector

2
Technical Data (T ambient = 25 °C, U S = DC 24 V)
Terminals
aux. contacts
screw terminals
max. cable cross section
flexible with wire end ferrule w/wo plastic sleeve
wire stripping length
tightening torque (EN 60934)
Housing material
moulded
Mounting
symmetrical rail to EN 60715-35x7.5
Ambient temperature
0...+50 °C (without condensation, see
EN 60204-1)
Storage temperature
-20...+70 °C
Humidity
96 hrs/95 % RH/40 °C to
IEC 60068-2-78, test Cab.
climate class 3K3 to EN 60721
Vibration
3 g, test to IEC 60068-2-6 test Fc
Degree of protectio
housing: IP20 EN 60529
terminals: IP20 EN 60529
EMC (EMC directive,
emission: EN 61000-6-3
CE logo)
susceptibility: EN 61000-6-2
Insulation co-ordination
0.5 kV/2 pollution degree 2
(IEC 60934)
re-inforced insulation in operating area
dielectric strength
max. DC 32 V (load circuit)
Insulation resistance
n/a, only electronic disconnection
(OFF condition)
Dimensions (W x H x D)
12.5 x 80 x 83 mm
Mass
approx. 65 g
Schematic diagram ESX10-TB-124 (Example)
LINE (+)
DC 24 V
LOAD (+)
0 V
load output
Time/Current characteristic curve (T A = 25 °C)
disconnection
typically 1.1 x I N
10000
1000
100
10
5
1
0.1
0.01
0
1
M3
0.25 – 2.5 mm
8 mm
0.5 - 0.6 Nm
S1
ON/OFF
status indication
green/orange/red
RE reset input
SF status output
1.8 x I N
current limitation
typically 1.8 x I N
4
2
3
...times rated current
ESX10-T Signal inputs / outputs (wiring diagram)
ESX10-T signal inputs / outputs (schematic diagrams)
Auxiliary contacts are shown in OFF or error condition
ESX10-TA-100
2
without signal input/output
LINE+ 1
2
LOAD+
0V 3
ESX10-TB-102
without signal input
with signal output F
(single signal, N/C)
LINE+ 1
12
11
operating
2 LOAD+
condition:
11-12 open
fault condition:
11-12 closed
0V 3
ESX10-TB-124
with reset input RE
(+DC 24 V ↓ )
with status output SF
(+24 V = load output ON)
LINE+ 1
SF 23
RE 22
operating
2 LOAD+
condition:
SF +24 V = OK
fault condition:
SF 0 V
0V 3
The trip time is typically 3 s in the range between 1.1 and 1.8 x I
l
(e.g. ESX10-TB-...-6 A)
Electronic current limitation I
l
which means that under all overload conditions (independent
of the power supply and the resistance of the load circuit)
the max. overload before disconnection will not exceed 1.8
x I
times the current rating. The individual current limitation
N
value I
depends on the current rating (see table1). Trip
Limit
time is between 100 ms and 3 sec (depending on overload
or at short circuit).
Without this current limitation a considerably higher overload
l
current would flow in the event of an overload or short circuit.
5
IK
- 3 -
ESX10-TB-101
without signal input
with signal output F
(single signal, N/O)
LINE+ 1
14
13
operating
2
condition:
LOAD+
13-14 closed
fault condition:
13-14 open
0V 3
ESX10-TB-114
with control input IN+
(+DC 24 V)
with status output SF
(+24 V = load output ON)
LINE+ 1
SF 23
IN 21
operating
2 LOAD+
condition:
SF +24 V = OK
fault condition:
SF 0 V
0V 3
ESX10-TB-127
with reset input RE
(+DC 24 V ↓ )
with inverse status output SF
(0 V = load output ON)
LINE+ 1
SF 23
RE 22
operating
2 LOAD+
condition:
SF 0 V = OK
fault condition:
SF +24 V
0V 3
occurs at typically 1.8 x I
Limit
N
N