Technical Data and Specifications
The bridge between the three neutral terminal poles (N1, N2, N3) must be removed
before the three incoming active lines are connected.
• The first incoming active is connected to terminals A1 and N3.
• The second incoming active is connected to terminals A2 and N1.
• The third incoming active is connected to terminals A3 and N2.
This connection is ILLEGAL in Australia, Europe and the U.K.
This connection renders the output socket's neutral pins LIVE.
Note that a dimmer wired in this fashion will be subjected to CONTINUOUS
OVERVOLTAGE if connected to the 415V wye or star three-phase supply of most
countries.
The three active lines must each be protected at not more than the specified maximum.
The earth conductor must be rated the same as the active lines.
Revision 0.1 – 3 June 1999