Remote controller setting
1.
Turn on all of the indoor units.
*
1
Turn on the indoor unit with the unit number 0 last.
(Within 1 minute)
*
2
When the indoor units are turned on, error codes
01 and 31 will be displayed; however, these error
codes will be deleted by setting the remote controller.
Therefore, continue with the setting procedure.
2.
Set the refrigerant circuit address. (Assign the same
number to all of the indoor units connected to an
outdoor unit.)
Refrigerant circuit
address
3.
Set the "master" and "slave" settings. (Set the indoor
unit that is connected to the outdoor unit using a trans-
mission cable as the "master".)
Master
Slave
4.
After completing the function settings, turn off all of the
indoor units, and then turn them back on.
*
If error code 01, 1F, 30, 31, or 32 is displayed, there
may be an incorrect setting. Perform the remote
controller setting again.
NOTE
When different indoor unit models are connected using the
group control system, some functions may no longer be avail-
able.
If the group control system contains multiple units that are
operated simultaneously, connect and set the units as shown
below.
Standard
pair
Outdoor
unit ①
Remote
Indoor
controller
unit
DIP switch setting
0
(Indoor unit)
Remote controller
setting
00
adress
00
・Master/Slave
: Transmission cable, Power supply cable
: Remote controller cable
*Make sure that the indoor unit with the unit number 0 is con-
nected to the outdoor unit using a transmission cable.
En-16
Function Number
Setting Value
02
00~15
Function Number
Setting Value
51
Simultaneous
Simultaneous
twin
triple
Outdoor
Outdoor
unit ②
unit ③
Indoor
Indoor
Indoor
Indoor
unit
unit
unit
unit
1
2
3
01
01
02
02
00
01
00
01
: Power supply cable
: Bus wire
www.enindel.com

14. FRESH-AIR INTAKE

(1)
Open up the knockout hole for the fresh-air intake, as
shown in the figure. (If using half-concealed installation,
open up the top knockout hole instead.)
When removing the cabinet (iron plate), be careful not
to damage the indoor unit internal parts and surrounding
area (outer case).
00
When processing the cabinet (iron plate), be careful not
01
to injure yourself with burrs, etc.
(2)
Fasten the round flange (optional) to the fresh-air intake,
as shown in the figure. (If using half-concealed installation,
attach to the top.)
[After completing "3. INSTALLATION WORK"...]
(3)
Connect the duct to the round flange.
(4)
Seal with a band and vinyl tape, etc. so that air does not
leak from the connection.
Indoor
unit
4
5
02
01

15. CUSTOMER GUIDANCE

Explain the following to the customer in accordance with the
operating manual:
(1)
Starting and stopping method, operation switching, tem-
perature adjustment, timer, air flow switching, and other
remote control unit operations.
(2)
Air filter removal and cleaning, and how to use the air
louvers.
(3)
Give the operating and Installation Manuals to the cus-
tomer.
(4)
If the signal code is changed, explain to the customer how
it changed (the system returns to signal code A when the
batteries in the remote control unit are replaced).
*(4) is applicable to using wireless remote control.
For half concealed
installation
Indoor unit
CAUTION
Round duct (option parts)
Duct