Fujitsu AG*F12LAC 사용 설명서 - 페이지 9

{카테고리_이름} Fujitsu AG*F12LAC에 대한 사용 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Fujitsu AG*F12LAC 42 페이지. Indoor unit

Fujitsu AG*F12LAC 사용 설명서
6. CAPACITY TABLE
6-1. COOLING CAPACITY
MODEL : AGF09LA
AFR
9.5
18
°CDB
12
°CWB
°CDB
TC
SHC
20
1.99
1.88
25
2.27
2.15
30
2.16
2.05
35
2.05
1.94
40
1.90
1.80
43
1.87
1.77
MODEL : AGF12LA
AFR
9.5
18
°CDB
12
°CWB
°CDB
TC
SHC
20
2.67
2.17
25
3.05
2.48
30
2.91
2.37
35
2.76
2.25
40
2.56
2.08
43
2.52
2.05
MODEL : AGF14LA
AFR
10.8
°CDB
18
°CWB
12
°CDB
TC
SHC
20
3.42
2.61
25
3.66
2.80
30
3.50
2.67
35
3.32
2.53
40
2.94
2.25
43
2.78
2.12
3
AFR : Air Flow Rate (m
/min)
TC : Total Capacity (kW)
SHC : Sensible Heat Capacity (kW)
P I :
Input
Power
(kW)
21
23
15
16
P I
TC
SHC
TC
SHC
P I
0.25
2.21
1.89
0.25
2.29
2.05
0.41
2.53
2.16
0.42
2.61
2.35
0.46
2.41
2.06
0.47
2.49
2.24
0.51
2.29
1.95
0.52
2.37
2.12
0.53
2.12
1.81
0.54
2.19
1.97
0.54
2.08
1.78
0.55
2.15
1.93
21
23
15
16
P I
TC
SHC
P I
TC
SHC
0.45
2.98
2.19
0.45
3.08
2.38
0.74
3.40
2.50
0.75
3.52
2.72
0.82
3.24
2.38
0.83
3.36
2.59
0.91
3.08
2.26
0.92
3.18
2.46
0.95
2.86
2.10
0.96
2.95
2.28
0.96
2.80
2.06
0.97
2.90
2.24
21
23
15
16
P I
TC
SHC
P I
TC
SHC
0.62
3.81
2.63
0.63
3.94
2.86
0.91
4.08
2.81
0.92
4.22
3.06
1.00
3.90
2.69
1.02
4.03
2.92
1.10
3.70
2.55
1.12
3.82
2.77
1.14
3.28
2.26
1.16
3.39
2.46
1.16
3.10
2.13
1.17
3.20
2.32
Indoor temperature
25
27
18
19
P I
TC
SHC
P I
TC
SHC
0.26
2.44
2.06
0.26
2.51
2.23
0.42
2.79
2.35
0.43
2.87
2.54
0.47
2.66
2.24
0.48
2.74
2.42
0.52
2.52
2.13
0.53
2.60
2.30
0.55
2.34
1.98
0.55
2.41
2.13
0.55
2.30
1.94
0.56
2.37
2.10
Indoor temperature
25
27
18
19
P I
TC
SHC
P I
TC
SHC
0.45
3.28
2.39
0.46
3.38
2.58
0.75
3.75
2.73
0.76
3.87
2.94
0.84
3.58
2.60
0.85
3.69
2.81
0.93
3.39
2.47
0.94
3.50
2.66
0.97
3.15
2.29
0.98
3.25
2.47
0.98
3.09
2.25
0.99
3.19
2.43
Indoor temperature
25
27
18
19
P I
TC
SHC
P I
TC
SHC
0.63
4.20
2.87
0.64
4.33
3.10
0.93
4.50
3.07
0.93
4.64
3.31
1.02
4.30
2.93
1.03
4.43
3.16
1.12
4.07
2.78
1.13
4.20
3.00
1.17
3.61
2.47
1.18
3.73
2.66
1.18
3.41
2.33
1.19
3.52
2.51
- (01 - 08) -
29
32
21
23
P I
TC
SHC
P I
TC
SHC
0.26
2.67
2.22
0.26
2.82
2.36
0.43
3.04
2.53
0.43
3.22
2.70
0.48
2.90
2.41
0.48
3.07
2.57
0.53
2.76
2.29
0.54
2.91
2.44
0.55
2.56
2.13
0.56
2.70
2.26
0.56
2.51
2.09
0.57
2.65
2.22
29
32
21
23
P I
TC
SHC
P I
TC
SHC
0.46
3.59
2.57
0.47
3.79
2.73
0.76
4.10
2.93
0.77
4.33
3.12
0.85
3.91
2.79
0.86
4.13
2.98
0.94
3.71
2.65
0.95
3.92
2.83
0.98
3.44
2.46
0.99
3.63
2.62
0.99
3.38
2.42
1.00
3.57
2.57
29
32
21
23
P I
TC
SHC
P I
TC
SHC
0.64
4.59
3.08
0.65
4.85
3.28
0.94
4.91
3.30
0.95
5.19
3.51
1.04
4.69
3.15
1.05
4.96
3.36
1.14
4.45
2.99
1.15
4.70
3.18
1.19
3.95
2.65
1.20
4.17
2.82
1.20
3.73
2.50
1.21
3.94
2.67
P I
0.27
0.44
0.49
0.54
0.57
0.57
P I
0.47
0.78
0.87
0.96
1.00
1.01
P I
0.66
0.96
1.06
1.16
1.21
1.22