{카테고리_이름} Fujitsu AGU12RLF에 대한 빠른 시작 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Fujitsu AGU12RLF 2 페이지. Heating / cooling lockout setting
Fujitsu AGU12RLF에 대해서도 마찬가지입니다: 서비스 게시판 (3 페이지), 엔지니어링 게시판 (2 페이지)

Fujitsu AGU12RLF 빠른 시작 매뉴얼
Heating / Cooling Lockout Setting
ASU9RLF, ASU9RLF1, ASU9RLS2, ASU9RLS3, ASU9RL2, ASU12RLF, ASU12RLF1, ASU12RLS2, ASU12RL2,
ASU15RLS, ASU15RLS3, ASU18RLB, ASU18RLF, ASU24RLF, ASU24RLB, ASU24RLXB, ASU30RLXB,
ASU30RLX, ASU36RLXB, ARU9RLF, ARU12RLF, ARU18RLF, AUU9RLF, AUU12RLF, AUU18RLF, AGU9RLF,
This new setting for the systems will allow you to lockout a specific mode. Once function is set the
wireless remote will still display the locked out mode, but indoor unit will beep twice and all LED lights
will flash to indicate function locked out.
You will find instructions on how to set this function on page 2.
Fixed operation mode switching
Sets the operation mode to heat pump, heating only, or cooling only.
Disclaimer:
In order to perform some of these tests an electrical and/or refrigerant license is required. We strongly advise to check the Service manual for more detailed explanation. If you are not sure about these recommendations please contact us at 866-952-8324.
AGU12RLF, AGU15RLF
Function Number
94
Engineering Bulletin
Applies to models:
Setting Value
Setting Description
00
01
02
© 2015 Fujitsu General America, Inc.
by
(* Factory setting)
Heat pump*
Heating only
Cooling only
# 054
4/23/15