F. Faults of temperature Sensors
Designation of sensors
Indoor ambient temperature
Indoor tube temperature
Outdoor ambient temperature
Outdoor tube temperature
8
Exhaust
Overload
The sensor is detected to the open-circuited or
short-circuited for successive 5 seconds
The sensor is detected to the open-circuited or
short-circuited for successive 5 seconds
The sensor is detected to the open-circuited or
short-circuited for successive 30 seconds
The sensor is detected to the open-circuited or
short-circuited for successive 30 seconds and no
detection is performed within 10 minutes after defrost
After the compressor has operated for 3 minutes the
sensor is detected to the open-circuited or
short-circuited for successive 30 sec
After the compressor has operated for 3 minutes the
sensor is detected to the open-circuited or
short-circuited for successive 30 sec
Faults
begins.