A-Plus Water Duraline series 서비스 매뉴얼 - 페이지 12

{카테고리_이름} A-Plus Water Duraline series에 대한 서비스 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. A-Plus Water Duraline series 13 페이지. Air iron system w/air pump for h2s, manganese and iron reduction

 Fully Automatic
 Self-Cleaning Backwash
 Service Flow of 7 GPM
 Working pH: 6.8-9
 Removes:
Clear Iron up to 15 ppm
Red Iron up to 8 ppm
Manganese up to 2 ppm
Sulfides (Sulfur) up to 4 ppm
Air Injection Oxidation
Aeration injects dissolved oxygen to convert the iron and manganese from their ferrous and manganous forms to their insoluble
form. It takes 0.14 ppm of dissolved oxygen to oxidize 1 ppm of iron; it takes 0.27 ppm of dissolved oxygen to oxidize 1 ppm of
manganese.
The air injection process requires careful control of the flow. If water usage becomes to great, not enough air is applied to oxidize
the iron and manganese. The advantage of the Hankscraft Iron Removal System is that the aeration is adjustable from immediate
on demand to delayed aeration based on real time water usage and the oxidation process can be optimized.
R00030-IRON REMOVAL SYSTEM
PART #
R0008*
IRON REMOVAL KIT
PTN10-54
10X54 NATURAL PRESSURE TANK
PTT10-54
10X54 DISTRIBUTOR TUBE W/ LOWER BASKET
R-GFM
GRANULAR FILTER MEDIA
R-FILAG
FILTER AG
Also available as R00028 using 9 x 48 tanks w/ 1cu/ft. total media.
DESCRIPTION
QTY
1
2
2
0.625
0.625