Kohler 10RESVL 설치 매뉴얼 - 페이지 16

{카테고리_이름} Kohler 10RESVL에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Kohler 10RESVL 48 페이지. Residential/commercial generator sets
Kohler 10RESVL에 대해서도 마찬가지입니다: 설치 지침 (2 페이지)

Kohler 10RESVL 설치 매뉴얼
1.7.3

Connecting the Fuel Supply

The dimension drawing in Section 3 shows the location
of the fuel inlet connection. Have the fuel supplier install
rigid gas piping and a manual fuel shut-off valve. The
fuel supply line should line up with the generator set fuel
inlet and end about 12 inches away to allow connection
with a section of flexible fuel line. Use flexible sections to
prevent fuel line breakage caused by vibration.
Note: Do not bend the flexible fuel line to make up for
misalignment of the fuel supply line and the
generator set fuel inlet.
Apply pipe sealant that is approved for fuel connections.
Hold the fuel solenoid valve with a wrench when
tightening the fuel connections.
Note: Do not hold the fuel solenoid valve coil when
tightening the fuel connections. See Figure 1-8
for the recommended wrench locations.
Open the manual fuel valves and test all fuel
connections using soapy water. If a leak is found, close
the fuel valves, clean the fittings, and apply fresh
sealant. Check for fuel leaks again with the generator
set running.
Fuel Type
% Load
100%
75%
Natural Gas
50%
25%
100%
75%
LPG
50%
25%
LPG conversion factors:
3
8.58 ft.
= 1 lb.
3
0.535 m
= 1 kg
3
36.39 ft.
= 1 gal.
Figure 1-9 Fuel Consumption
16
Section 1 Installation
8RESV/RESVL
60 Hz
3.9
(136)
2.7
(95)
2.0
(69)
1.5
(53)
1.7
(59)
1.3
(45)
1.0
(36)
.75
(26)
Nominal fuel rating:
3
Natural gas:
37 MJ/m
3
LPG:
93 MJ/m
Protect all fuel lines from machinery or equipment
contact, adverse weather conditions, and environmental
damage.
1
1. Hold valve with wrench on flats of valve body
2. Alternate wrench location
Note:
Do NOT hold the valve coil when tightening connections.
Figure 1-8 Holding Fuel Valve to Tighten Fuel
Connections
3
Fuel Consumption, m
10RESV/RESVL
60 Hz
5.1
(179)
4.1
(145)
3.4
(120)
2.7
(97)
2.5
(89)
2.0
(69)
1.5
(52)
1.1
(39)
3
(1000 Btu/ft.
)
3
(2500 Btu/ft.
)
/hr. (cfh)
12RESV/RESVL
60 Hz
6.1
(216)
4.5
(160)
3.6
(128)
2.8
(99)
2.9
(103)
2.2
(76)
1.6
(57)
1.2
(42)
TP-6984
2
5/17a