1.15.1 Voltage Regulator

Displays the voltage regulator adjustment, volt/Hz, gain,
and stability adjustment values.
The voltage regulator value is reviewable at all times
and provides the ability to fine adjust voltage. Changing
the system voltage or replacing the circuit board
typically requires a voltage adjustment.
To enable calibration, start the generator set and select
the VR Volt Adj, Volt/Hz, Gain, or Stability display. Then
Voltage Regulator
Voltage ---->
Regulator
User Selectable - ->

1.15.2 Event Log

Displays up to 1000 stored status, warning, and
shutdown events. After the first 1000 events, each
additional new event replaces the oldest event.
Event Log
Event Log ---->
6
VR Volt Adj:
xxx.x
VR Volt/Hz:
xxx.x
VR Gain:
xxx.x
VR Stabil:
xxx.x
Reset VR
-->
Settings
#####
(Message Text)
(Scroll through up to 1000
max. stored events)
push and hold the pushbutton/rotary selector dial until
the Editing Enabled popup appears. Editing of the
voltage adjustment is now available.
The user can change the individual value or can select
Reset VR?- -Yes to reset to the default value. The Reset
VR Settings display will only show if editing is enabled.
To disable calibration, Rotate the pushbutton/rotary
selector dial until the <- -Return popup appears.
Momentarily press the pushbutton/rotary selector dial.
Stop the generator set if not already done.
Reset VR?
No
OR
Reset VR?
Yes