4.5 Controller Troubleshooting
Figure 4-3 contains troubleshooting, diagnostic, and
repair information for the Advanced Digital Control.
Problem
Possible Cause
Controller LED
Controller may power down if the generator set
display is off
has not run in the last hour of 48 hours,
depending on the controller's Cn parameter
setting. See Section 2.3.6, Controller Power
Down.
Controller fuse (F3) is blown.
Low or no battery voltage.
Generator set master switch is in the
OFF/RESET position.
Figure 4-3 ADC 2100 Troubleshooting Chart
TP-6728 10/11
Corrective Action
Controller display will automatically activate when a
remote start command is received or the generator
set master switch is moved to the RUN position.
Replace the fuse. If the fuse blows again, contact
the distributor/dealer.
Check connections.
Check generator set battery. See Figure 4-2.
Move generator set master switch to the AUTO or
RUN position.
Section 4 Troubleshooting
33