Kohler 18RESHD 설치 매뉴얼 - 페이지 18
{카테고리_이름} Kohler 18RESHD에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Kohler 18RESHD 40 페이지. Residential/commercial generator sets
Kohler 18RESHD에 대해서도 마찬가지입니다: 운영 (48 페이지)
1.4.1
Exhaust Requirements
WARNING
Carbon monoxide.
Can
cause
fainting, or death.
The
exhaust
leakproof and routinely inspected.
Generator set operation. Carbon monoxide can cause
severe nausea, fainting, or death. Carbon monoxide is an
odorless, colorless, tasteless, nonirritating gas that can cause
death if inhaled for even a short time. Avoid breathing exhaust
fumes when working on or near the generator set. Never
operate the generator set inside a building. Never operate the
generator set where exhaust gas could seep inside or be
drawn into a potentially occupied building through windows, air
intake vents, or other openings.
The exhaust system is complete for generator sets
installed outdoors. Do not install this generator set
indoors.
Figure 1-6 gives the exhaust flow and temperature at
rated load.
The engine exhaust mixes with the
generator set cooling air at the exhaust end of the
enclosure. Mount the generator set so that the hot
exhaust does not blow on plants or other combustible
materials. Maintain the clearances shown in Figure 1-5.
Exhaust System
Exhaust flow at rated kW,
3
m
/min. (cfm)
12 kW
17/18 kW
Exhaust gas temperature exiting
the enclosure at rated kW, _C (_F)
Figure 1-6 Exhaust Flow and Temperature
1.4.2
Air Requirements
The generator set requires correct air flow for cooling
and combustion. The inlet and outlet openings in the
sound enclosure provide the cooling and combustion
air. Figure 1-7 shows the locations of the cooling air
intake and exhaust vents. Inspect the air inlet and outlet
openings inside and outside the housing to ensure that
the air flow is not blocked.
18
Section 1 Installation
severe
nausea,
system
must
be
60 Hz
3.8 (135)
5.3 (187)
216 (420)
1
2
1. Exhaust outlet
2. Alternator air intake (both sides)
3. Engine air intake
Figure 1-7 Cooling Air Intake and Exhaust
Air Requirements,
Cooling
Air
Hz
Model
60
26.9 (950)
12 kW
50
22.4 (790)
60
28.0 (989)
17/18
kW
50
22.6 (798)
Figure 1-8 Air Requirements
1.5 Power Supply
Power must be supplied from a source that is GFCI
protected to the generator set location for the battery
charger and the optional carburetor heater.
Section 1.8. Connect power from a circuit on the
essential loads panel to the 120-VAC receptacles.
Figure 1-9 lists the power requirements for the battery
charger and accessories.
Watts
Equipment
Battery charger
Carburetor heater:
12 kW
17/18 kW
Battery heater
Figure 1-9 Power Requirements
3
3
GM51561
3
m
/min. (cfm)
Combustion
Total Inlet
Air
Air
1.1 (39.2)
28.0 (990)
0.9 (32.6)
23.4 (826)
1.62 (57.3)
29.6 (1045)
1.42 (50.1)
24.0 (848)
Power Requirement, Max.
Amps
Volts
192
1.6
38
0.32
120
40
0.34
110
0.92
TP-6516 4/09
See