1.3 Generator Set Inspection

Complete a thorough inspection of the generator set.
Check for the following:
1. Inspect the generator set for loose or damaged
parts or wires. Repair or tighten any loose parts
before installation.
2. Check the engine oil. Fill, if necessary, with the
recommended viscosity and grade of oil. Use
synthetic oil, API (American Petroleum Institute)
Service Class SG or higher.
Operation Manual, for additional information.

1.4 Location and Mounting

Install the generator set outdoors. Choose a location
that is away from any building or structure and near
the incoming gas service. Allow clearance beyond the
exhaust end of the generator set.
generator set so that the hot exhaust does not blow on
plants or other combustible materials. Do not install
the
generator
set
accumulate and seep inside or be drawn into a
potentially occupied building.
Refer to your local codes and ordinances. See
Figure 2-5 for more details.
Notice
DO NOT locate the generator set near patios,
decks, play areas, or animal shelters. Keep items
such as lawn furniture, toys, sports equipment, and
all combustible materials away from the generator
set exhaust outlet.
Remind family members, children, and visitors to
use caution near the generator set. Generator sets
will start automatically during exercise periods and
power outages. Some generator set components
become hot when the generator set is running and
remain hot for a time after the generator set shuts
down.
1.4.1

Mounting Area

Install the generator set on a single, level concrete
mounting pad.
This method provides maximum
stability and ensures correct cooling air flow through
the generator set. The recommended mounting pad
dimensions are shown in the dimension drawings in
Section 2.
12
Section 1 Installation
See TP-6843,
Locate the
where
exhaust
gas
1.4.2

Vibration Isolation

The generator set is equipped with neoprene vibration
isolators. Connections between the generator set or
its mounting base and any conduits or fuel lines must
include flexible sections to prevent breakage and to
isolate vibration.
1.4.3

Exhaust Requirements

Figure 1-2 gives the exhaust temperature at rated
load. The engine exhaust mixes with the generator set
cooling air at the exhaust end of the enclosure. Mount
the generator set so that the hot exhaust does not
blow on plants or other combustible materials.
Maintain the clearances shown in Figure 2-5.
Figure 1-2
Exhaust
Exhaust gas exiting the enclosure at
rated kW, °C (°F)
Figure 1-2
could
The generator set requires correct air flow for cooling
and combustion. The inlet and outlet openings in the
sound enclosure provide the cooling and combustion
air. Inspect the air inlet and outlet openings inside and
outside the housing to ensure that the air flow is not
blocked.

1.5 Dimension Drawings

See the dimension drawings in Figure 2-3 through
Figure 2-5 for the generator set dimensions, fuel and
electric inlet locations, and recommended clearance.

1.6 Fuel Requirements

The generator set operates using natural gas or LPG
fuel.
The generator set is EPA-certified for both
natural gas and LPG fuels.
The fuel system installation must comply with the NEC
and local codes.
Exhaust Flow and Temperature
Temperature,
°C (°F)
110 (230)
TP-6842 7/15