Safety Precautions
Observe the following safety precautions while
installing the kit.
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working
on
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set.
cause severe injury or death.
generator set or equipment connected to the set, disable the
generator set as follows: (1) Shut down the generator set. (2)
Place the controller in Out of Service mode. (3) Press the
emergency stop button. (4) Disconnect the power to the
battery charger, if equipped. (5) Remove the battery cables,
negative (--) lead first. Reconnect the negative (--) lead last
when reconnecting the battery. Follow these precautions to
prevent the starting of the generator set by the remote
start/stop switch.
DANGER
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening the enclosure.
2
the
generator
set.
Accidental starting can
Before working on the
Installation Procedure
1. Before working on the generator set or connected
equipment, disable the generator set. Refer to the
safety precautions for preventing accidental starts
and disabling the generator set.
a. Remove the load from the generator set.
b. Shut down the generator set.
c. Place the generator set controller into
Out-of-Service
emergency stop button.
d. Disconnect the power to the battery charger.
e. Remove the battery cables negative (--) lead
first to disable the generator set.
2. To access the terminal block, TB10, remove the
eight screws from the lower compartment cover on
the control panel. See Figure 3.
3. Remove jumper from terminals TB10-1 and 2.
1
1. Lower compartment
cover
2. TB10
3. 38 mm (1-1/2 in.) holes
Figure 3 Lower Compartment Component Location
mode
and
press
3
TT-1719
12/16
the
2