1. DESCRIPTION

The A-LEGIO SENSE panel has been designed to control the proliferation of legionella and other hydrodiffused
pathogens through an ON / OFF or proportional dosage of sodium hypochlorite or chlorine dioxide at the same
time as a dosage of an anticorrosive conditioner.
In general, it is composed of:
1 AE-START + CL instrument for the measurement of free chlorine;
1 pump HC151 + (PImA model) to dose an inhibitor (anticorrosive) product controlled by a pulse-
emitting counter;
1 pump HC151 + (PimA model) with automatic air purge to dose a disinfectant product (sodium
hypochlorite, etc.) controlled by the AE-START + CL instrument;
1 membrane amperometric probe for the determination of free chlorine;
1 modular HT probe holder, proximity sensor and flow regulator;
1 HT prefilter.
For the pump managed by the chlorine measuring instrument, the dosage mode set in the factory is the
proportional one: the dosage is proportional to two mA values (4mA and 20mA).
1.1

PANEL COMPOSITION

Panel
Membrane chlorine probe 0-5ppm
n. 1 temperature probe (optional)
HT water filter 9"3/4 complete of AC-HT cartridge 80 micron, 10x14 tube fittings
Roll of PVC tube 10X14 (4m)
Controller, pump and panel programming manuals
n.2 PVDF injection valve
n.2 PVDF foot filter
Roll of PE tube for delivery (4 m)
Roll of PVC tube for suction (4 m)
Roll of PVC tube for air bleed (4 m)
1.2

TECHNICAL SPECIFICATIONS

Supply:
Panel dimensions:
Max power:
110-240VAC – 50/ 60Hz
L 650 x H 600 x D 250 mm
60 W (with pumps in "C" curve)
ENGLISH
4/12