7.3 Testing Procedure
Note: Avlite recommends that all testing be done during the day. TPower the system on.
1.
Check that no circuit breakers have tripped.
2.
Cover each light fixture in the low intensity obstruction light and ensure they turn on.
3.
Uncover each light fixture in the low intensity obstruction light and ensure they turn off.
4.
For 01 & 02 Variants only:
Trip the breaker for the low intensity light fixture and ensure that the
corresponding alarm is received (if monitoring is installed)
8.0 Maintenance and Servicing
Refer to the individual light manuals for light maintenance.
Inspect the Control Unit for evidence of dust or water penetration. Repair gaskets or
conduit entries as required.
Inspect Control wiring for failing insulation, open conductors or other wiring flaws and
repair as required.
9.0 Replacement Parts
If replacement parts are required, please call a local Avlite distributor and reference the
Product or Configuration Code called out in the "Product Configuration and Options" section