Helios 6 / 8 Installation
220-240V / 50-60Hz
IP20
Terminal Labelling:
Power
L1
Switched Live
E
Earth
N
Neutral
Emergency
L2
Unswitched Live
DA/AT3
DALI Autotest
DA/AT3
DALI Autotest
Dimming
-/D1/DA
Analogue/DSI/DALI
+/D2/DA
Analogue/DSI/DALI
L3
Switch Dim /
Corridor Function
1.
Helios 6
3.
5.
Maximum permissible loads:
Universal 3 circuit track adaptor: Maximum weight 10kg.
1M track length: Maximum load 60Kg
3M track length: Maximum load 90Kg
Loads should be evenly distributed across the length of track
- Universal track system suitable for 3 circuit, 230 / 240 Volt, 16 Amp. This system is not suitable for inductive loads.
- Please ensure that all elements of the track system have been correctly assembled, starts and ends must always have the
appropriate components to ensure that the run is correctly finished and live conductors are not exposed. Do not exceed
maximum loads or allow connection points to be subjected to twisting forces.
- It is the installer's duty to ensure electrical, mechanical and thermal compatibility between the track system and any
devices attached to it.
- The universal 3 circuit adapter supplied with the High Track luminaire is only suitable for use with the track system
specified.
- Track system is only suitable for surface mount or suspension via a rigid drop rod.
DIL-0179-0003
WARNING: Luminaire must be earthed. Risk of electric shock from LED boards if operated with cover
removed. Installation / operation outside of luminaires intended scope invalidates warranty. Suitable only for
domestic / light industrial / industrial applications within the scope of EN55015. Tested to compliance with
BSEN 60598: specification for general requirements and tests. Must be installed by a suitably qualified person
in accordance with all relevant legislation. Ambient operating temperature of 0°C to 25°C. If maximum
operating temperature is exceeded luminaire will automatically dim / switch off. Terminal blocks are rated to
16A unless stated otherwise. The light source contained in this luminaire shall only be replaced by the
manufacturer or his service agent or a similar qualified person. LUMINAIRES WITH EMERGENCY PACK:
When supply is isolated battery output terminals may be live if battery is connected. Isolate mains and battery
before servicing. Emergency luminaires require unswitched live connection taken from same phase as
switched supply. When unswitched supply is connected status indicator illuminates green, when unswitched
supply is disconnected indicator extinguishes and luminaire operates in emergency mode. 24 hour charge
period required before undertaking full discharge test. Emergency test sheets provided should be used to
record all emergency tests. Batteries should be replaced when 3 hour duration is not met. Excessive switching
of permanent live may result in premature battery failure. Battery electrolyte can be harmful to eyes / open
wounds, do not puncture, if electrolyte touches skin / eyes flush with water. Do not incinerate batteries.
2.
Helios 8
4.
3 Circuit Track Adaptor:
Connect three circuit track adaptor as per diagrams shown
to the left
1) Ensure the selector dial is turned to the off position.
2) Set the locking lever to the side
3) Engage the adaptor into the track with the guide lug.
4) Turn the lever towards the front until it locks correctly
with the track system.
5) Select the circuit by turning the selector dial to 1, 2 or 3.
6) Remove the adaptor by reversing the above process.
Revision - G