Warning sign
• It is of yellow colour with minimum dimensions of 100 × 200 mm
• It is either standard warning sign or contains the following
Inscription on both sides: ˝WARNING! ELECTRIC FENCE˝
• Letters must be at least 25 mm high and indelible
• One warning sign is included in the package contents
Power supply and connecting cables
• Cables that are rated for voltages higher than 1 kV and are located in buildings must be
effectively insulated from the building's earthing features. This may be achieved by using
insulated high-voltage cables or by leaving appropriate distance between the cable and the
building frame. Do not use standard electrical cables
• Cables that are laid in the ground (soil) must be protected by solid insulator pipes or use
insulated high-voltage cables designed for this purpose. Make sure that the cables will
not be damaged by, for example animal hooves or tractor wheels, which can sink into the
ground. Do not use standard electrical cables.
• Cables must not be placed in pipes together with other circuit, communication or data cables.
Supply and connecting leads and electric line of fence system:
• Shall not cross above overhead power or communication lines. Crossings with overhead
power lines shall be avoided wherever possible. If such a crossing cannot be avoided it shall
be made underneath the power line and as nearly as possible at right angles to it.
• If are installed near an overhead power line, the clearances shall not be less than those shown.
Power line voltage
≤ 1000 V
> 1000 ≤ 33000 V
> 33000 V
• If are installed near an overhead power line, their height above the ground shall not exceed
3 m. This height applies to either side of the orthogonal projection of the outer most condu-
ctors of the power line on the ground surface, for a distance of:
• 2 m for power lines operating at a nominal voltage not exceeding 1000 V
• 15 m for power lines operating at a nominal voltage exceeding 1000 V
• Being nearby telephone line or telephone cable, must be conducted at a distance of mini-
mum of 2 metres.
Electric animal fences intended for deterring birds household pet containment or training
animals such as cows need only be supplied from low output energizers to obtain satisfactory
and safe performance.
In electrical animal fences intended for deterring birds from roosting on buildings no fence
wire shall be grounded if the fence wires are not connected to metal parts. If one wire is
connected with a metal part (ie a gutter) or a metal structure of the building these metal parts
must be grounded. A warning sign shall be fitted to every point where persons may gain ready
access to the conductors.
Where an electric animal fence crosses a public pathway, a non-electrified gate shall be
incorporated in the electric animal fence at that point or a crossing by means of stiles shall be
provided. At any such crossing, the adjacent electrified wires shall carry warning signs.
14
Clearance
3 metres
4 metres
8 metres