AB Quality 1769-IQ16F 설치 지침 매뉴얼 - 페이지 11
{카테고리_이름} AB Quality 1769-IQ16F에 대한 설치 지침 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. AB Quality 1769-IQ16F 16 페이지. Compact 16-point 24v dc sink/source high-speed input module
3. Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.68 Nm (6 in-lbs).
TIP
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
Wire Type
Solid
Cu-90°C (194°F)
Stranded
Cu-90°C (194°F)
I/O Memory Mapping
Input Data File
For each input module, slot x, word 0 in the input data file contains the current
state of the field input points.
15
14
13
0
r
r
r
r= read
Compact 16-point 24V dc Sink/Source High-speed Input Module
If you need to remove the finger-safe cover, insert a
screw driver into one of the square, wiring holes and
gently pry the cover off. If you wire the terminal block
with the finger-safe cover removed, you will not be able
to put it back on the terminal block because the wires
will be in the way.
Wire Size
#14 to #22 AWG
#16 to #22 AWG
12
11
10
9
r
r
r
r
Terminal Screw
Torque
0.68 Nm (6 in-lbs)
0.68 Nm (6 in-lbs)
Bit Position
8
7
6
5
r
r
r
r
Publication 1769-IN064A-EN-P - April 2003
Retaining Screw
Torque
0.46 Nm (4.1 in-lbs)
0.46 Nm (4.1 in-lbs)
4
3
2
1
r
r
r
r
11
0
r