1
Safety instructions
IMPORTANT! Please read these instructions carefully.
The manufacturer accepts no liability for any damage that
occurs because these instructions are not followed.
For future reference keep these instructions in the case
with the flushing system.
CAUTION
If the flushing system is connected to a low-pressure
system such as a boiler there is a risk of pressure build
up, causing leakage.
Before installing the flushing system check the water
outlet and associated pipework. If gaskets or joints
are damaged or unsecure, the additional weight of the
flushing system can cause leakage.
2
Instructions for fitting and initial operation
Only suitably qualified technicians using appropriate tools
should install and set-up the FLUSH 2.0 flushing system.
NOTE
The battery of the flushing system lasts for one year.
The date of the next battery change can be recorded
on the device itself using the stickers supplied.
In the event of battery failure the valve failsafe position
is CLOSED and the "DELAY", "FREQUENCY" and
"RUN TIME" LEDs on the display will flash repeatedly.
When the battery is changed the flushing program will
return to its default settings. The required programme
should be re-entered and then re-activated by pressing
the SET key for at least five seconds.
3
General instructions
3.1 Backflow protection
IMPORTANT! Before the flushing system is used with a
mixer tap or similar it is important to make sure non-return
valves are fitted.
2
WARNING
If the flushing system is used without non-return valves
being fitted or working, any back pressure from the
hot water supply risks contaminating the whole of the
drinking water supply system.
Non-return valves should be fitted on both the hot water
and cold water supply pipes to the tap.
The flushing system should not be used without
functioning non-return valves in place.
3.2 Storage
Dry all of the individual components before storage and
disconnect the battery. Store the components of the flushing
system in the case provided.
3.3 Disposal
Please dispose of the packaging for this product in an
environmentally friendly way. Do not dispose of batteries
with domestic refuse. Take them to special battery collection
points.
4
Product description
Aqua free has developed the FLUSH 2.0 flushing system
to automatically and individually flush water outlets that are
rarely used or left unused for periods of time. It prevents
water stagnation and the threat of microbial contamination in
the pipes.
FLUSH 2.0 can be easily installed on any taps, showers
or other water outlets in private homes, public buildings or
commercial establishments.
Recommendations for flushing cycles and flushing
duration:
If drinking water pipes are flushed daily Aqua free recom-
mends a flushing duration of 5 minutes.
However the precise duration depends on the cross section
and length of the pipe and the water pressure although
reference should always be made to national guidelines for
flushing.
3