APCO CVS-EDV Swing Check Valves
Operation
(Continued)
Adjustment (Valves with Air Cushion with Lever & Weight)
Condition
Unlock Flow Control Valve by turning valve lock nut counter-clockwise. Turn
adjustment screw of Flow Control Valve one-half (1/2) turn clockwise. Repeat
Check valve slams
start and stop. If slam persists, continue turning adjustment screw in ½ turn
increments. Be careful not to fully close Flow Control Valve. Lock Flow Control
Valve when finished.
Slam persists
Move weight towards end of lever a couple of inches. Repeat start and stop.
Continue repeating above steps until satisfactory closing is achieved. Then
increase opening discharge isolation valve to ½ open. Repeat start and stop
Slam still persists
pump sequence and above steps until isolation valve is full open. Lock Flow
Control Valve when finished.
Adjustment (Valves with Lever & Weight)
Condition
Check valve slams
Move weight towards end of lever a couple of inches. Repeat start and stop.
Slam persist
Repeat above step.
Notes:
1. Testing must be conducted carefully and adjustments made in small increments to arrive at the
optimum setting where the swing check valve shuts off just prior to or at zero reverse flow.
2. The APCO CVS-EDV Swing Check Valve is not a silent closing check valve.
D12042
Figure 2 – Adjustable Flow Control Valve
Page 10
Adjustment
Adjustment
February 2016