DeZurik G12-C8 매뉴얼 - 페이지 5
{카테고리_이름} DeZurik G12-C8에 대한 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. DeZurik G12-C8 16 페이지. Cylinder operated actuator
Actuator Identification
Adjusting Position Stops
The G-Series Cylinder Actuators have both open and closed position stops. See Figure 2 for position
stop identification.
The position stops are factory set and do not require adjustment unless the actuator has been
disassembled or actuator orientation has been changed.
Adjusting the Open Position Stop
On 6A and 12A cylinder actuators, the Open Position Stop is located in the end of the extension cap
opposite the cylinder. See Figure 2. The cylinder must be mounted before adjusting the position stop.
1. Open the valve and loosen the Open Position jam nut.
2. Adjust the Open Position set screw to the proper position.
3. Lock the Open Position set screw in place with the jam nut.
August 2012
(Continued)
Table A: Cylinder Identification
Cylinder
C4
C6
C8
C10
10.5
Figure 2 – Position Stops
Page 5
Cylinder Operated G-Series Actuator
"A"
IN
MM
4.5
115
6.5
165
8.5
215
265
DeZURIK
D10455