DeZURIK
Cylinder Operated G-Series Actuator

Removing Actuator

When eccentric valves are mounted in a vertical pipeline, or mounted in a horizontal pipeline with the
plug stem horizontal, gravity can cause the plug to swing to a lower position in the valve body when the
actuator is removed. To avoid this problem, place the plug in the lowest position before removing the
actuator.
1. Discontinue flow, relieve pipeline pressure and close valve.
Accidental operation of power actuator can cause personal injury or equipment damage.
Disconnect and lock out power to actuator before servicing.
2. Disconnect and lock out the pneumatic power to prevent accidental operation of the actuator.
3. Scribe corresponding lines on the valve and actuator to help align them during installation.
4. Remove screws (P3) and lift actuator assembly off adaptor (P1). See Figure 4 for connecting
parts identification.

Installing Actuator

1. Line up the scribe marks on the valve and actuator made
during actuator removal, then set the actuator on the valve
so that the valve shaft slides into the actuator gear sector.
2. Fasten the actuator assembly to the adaptor (P1) with
screws (P3). See Figure 4 for connecting parts
identification.
3. After actuator is mounted, and shaft key is assembled in
keyseat, secure shaft key by staking with a center-punch
on the end of the shaft. Stake on both sides of the shaft as
shown in Figure 5.
Note: Do not deform the outside diameter of the shaft.
D10455
Figure 4 – Connecting Parts Identification
Page 8
Figure 5 – Shaft Key Staking
August 2012