STEP1.
NOTE:
GAS CONNECTION
Make the gas connection between the manual shut offvalve and regulator located inside
heater cabinet. Hold regulator when tightening connection to prevent dmnage to regulator
and internal tubing. See Figure 6 for completed installation.
All piping and connection must be checked for leaks by the installer. If connections are not
exposed, a pressure test must be ran. The appliance and its individual shut offvalve must
be disconnected from the gas supply piping system during any pressure testing at pressures
in excess of ½ psig (3.5 kPa). The appliance must be isolated from the gas supply piping
system by closing its individual manual shut offvalve during any pressure testing of the gas
supply piping system at test pressures equal to or less than 1/2 psig (3.5kPa).
Outside Re_.
Internal Reaulator
Supplied
_
_lied)
_"
M_Union
\
{_- Drip Leg
1/8" NPT Plug
Manual
Cut off
Valve
Pressure
rl
GASPIPINGWITHVF-FSKKIT
FIGURE 6
FIGURE 6A
BURNER ORIFICE
This appliance
is orificed
at the factory
for elevations
up to 2,000 ft. If installed
above 2,000 ft. the BTU
input must be reduced
4% per 1,000 ft. See the following
orifice chart for the proper
orifice for a specific
elevation.
SPECIFIC
ELEVATION
Model
No.
0 to
2,000
-
4,000
-
6,000
-
8,000
-
No.
2,000'
4,000'
6,000'
8,000'
10,000'
NATURAL
GAS
BFT101
1.55 rain
54
54
55
55
BFT201
43
44
45
47
48
BFT301
36
38
40
41
43
L.E
GAS
BFT102
63
65
65
66
68
BFT202
55
55
56
56
57
BFT302
52
53
53
54
54